OMRON GX-ID1611 Product information and technical parameters:
Brand: OMRON
Name: EtherCAT Remote I/O Terminals
Model: GX-ID1611
Input capacity: 16 points.
Internal I/O common: NPN.
ON voltage: 15 VDC min.
(between each input terminal and the V terminal)
OFF voltage: 5 VDC max.
(between each input terminal and the V terminal)
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC);
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms, 1 ms,
2 ms, 4 ms, 8 ms, 16 ms, 32 ms (Default setting: 1 ms).
Number of circuits per common: 16 inputs/common.
Input indicators: LED display (yellow).
Isolation method: Photocoupler isolation.
I/O power supply method: Supply by I/O power supply.
Unit power supply current consumption: 90 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current con sumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 180 g max.
Expansion functions: Enabled.
Short-circuit protection function: No.
High-speed digital I/O terminal with the,
screw type terminal block for EtherCAT,
communications.
Detachable screw terminal block facilitates,
the maintenance.
The expansion unit can be connected.
(One expansion unit per one I/O terminal unit.)
Input/output point can be flexibly increased,
depending on the system.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary switch and with tool software.
When setting the nodes with rotary switch,
setting is easy and node identification becomes,
possible for maintenance.

Name: System Units; I/O Power Feed Unit.
Specifications: Use when the total current,
consumption of the I/O Power Supply exceeds 4 A,
or to make the I/O Power Supply a separate system.
Standards: CE, UC, L.
"Easy" and "Flexible" system expansion,
with linked CC-Link and CompoNet.
Branching is easily made with CompoNet GX-ID1611.
Wiring material cost can be reduced.
Bit-level I/O distribution reduces,
wiring in the system GX-ID1611
A wide variety of CompoNet Slave Units,
contribute to system size reduction.
Seven-segment Display on the Gateway Unit,
helps to detect errors on site.
The Participation Flags and Communications,
Error Flags can be checked at the Host,
Controller to detect the location and,
content of the error GX-ID1611. Specifications: Input, PNP (- common), 8 points.
I/O connections: Sensor I/O connector.
Rated internal circuit power supply voltage:
Supplied from the communications connector.
Rated I/O power supply voltage: Supplied from the communications connector.
Environment-resistive (IP67) I/O.
Terminals with Troubleshooting.
Functions such as Sensor Power.
Supply Short-circuit Detection GX-ID1611.
Equipped with the standard Smart Slave functions that provide powerful,
preventative maintenance and troubleshooting capabilities.
High degree of environmental resistance with dust-proof,
and drip-proofconstruction.
Power supply wiring is not required for input devices.
Connect heavy-load devices (up to 1.5 A).
Power supply wiring is not required for input devices such as sensors.
(Power supply wiring is required for output devices.)
Detects ground faults or disconnects and notifies the Master.
Unit: Connector model.
I/O classification: Digital output.
Internal I/O common: NPN (- common).
I/O points: 16.
I/O connectionns: Fujitsu connector GX-ID1611.
Power supplyvoltage: 24 VDC.
I/O specification: 0.5 A, DC/transistor.
Digital I/O Units Compatible with MULTIPLE I/O TERMINAL,
Terminal block, connector, and high-density connector,
models are available.
The ciircuit block of the terminal block model can be,
mounted or dismounted for ease of maintenance without,
disconnecting the wires GX-ID1611.