LK Automation Limited LK Automation Limited
Brand: OMRON
Go Back >> Product Catalogues
KM50-C1-FLK Intelligent power monitor
OMRON KM50-C1-FLK Manual And Instructions
KM50-C1-FLK datasheetPDF datasheet
KM50-C1-FLK (RS-485 CompoWay/F Communications)User's Manual
KM50-C1-FLK Communications Manual

OMRON KM50-C1-FLK Product information and technical parameters:
Brand: OMRON
Name: Intelligent power monitor
Model: KM50-C1-FLK
Type: KM50-C intelligent monitor.
Application circuit: single phase 2 wire system AC100 ~ 240V; single phase 3 wire system AC100/200V;
Three-phase 3 wire system AC100 ~ 240V.
Power supply voltage sharing: sharing AC100 to 240V with the measured voltage input.
Shape: 48 (H) * 48 (W) * 84 (D).
Communication: RS-485.
Protocol: ompoWay/F: the number of communication nodes 31 Modbus: the number of communication nodes 99 (shared).
Energy classification function (industry initiative).
Show the 3-STATE function through the 3 color display energy saving room for improvement.
Equipped with easy to grasp the room for energy saving and convenient 3-STATE function.
3-STATE function refers to the use of the state power, the cumulative power is divided into operation / standby / stop 3 types of functions.
2 and 3-STATE function linkage, can operate / standby / stop 3 points for individual output
(determine the object can be selected from power, current, voltage)
Pulse input count, pulse input ON time, unit power consumption measurement.

The ZN series is even thinner and,
sports improved air volume.
These products enable cleaning that,
is both fast and flexible.
Three sizes are available to match various sizes of clean booths. Product name: Branch cable (cable length 1.3 m).
Power supply: Battery/DC cable.
Easy and Quick "Checking Power"at the Worksite KM50-C1-FLK. Product name: Split type CT, Connector: For connecting the branch cable,
Cable length: 0 KM50-C1-FLK2 m.
Power supply: Battery/DC cable.
Easy and Quick "Checking Power"at the Worksite. Appearance: Sensor head: Anchored type.
Temperature: Measurement range, 0 to 60°C;
Measurement precision, ±0.3°C (at 25°C); Resolution, 0.1°C.
Relative humidity: Measurement range, 20 to 85%;
Measurement precision, ±2 KM50-C1-FLK. 5% (at 25°C, 10 to 85%); Resolution, 0.1%.
Weight (packaged): Approx. 300 g.
Accessories: Mounting screw (M3 x 8) x 1 Caps to secure cable,
(one for each, front and rear).
Easy temperature and humidity control with an SD Card. Item: Sensor head 1.5 m type.
Easy temperature and humidity control with an SD Card. Rated primary current: 100 A.
Rated secondary current: Special output KM50-C1-FLK.
Installation: Installed separately.
High-performance Power Monitor Suitable for On-panel Mounting and Display.
Assists Energy-saving Analysis.
Energy classification for wasted standby and stopped power.
(Classification based on external inputs is also supported.)
Power and current can be measured simultaneously.
Measurement of flow rates with a pulse conversion function.
Simple temperature measurements with Temperature Sensor included in the Unit.
High-precision Measurements.
Measurement of generated power (regenerative power),
leading reactive power, lagging reactive power, and consumed power.
Power measurements on the primary side of inverters,
which are widely used to save energy.
Automatic range switching for accurate measurement of standby and stopped power.
Energy-saving Functions.
Conversion to monetary cost. (Also used for classified standby and stoppedd power KM50-C1-FLK. )
Alarm outputs can be selected for active power, reactive power,
regenerative power, current, voltage, or power factor.
The Power Monitor can log measurement data and supports Modbus communications.
Installation and Settingss KM50-C1-FLK.
Direct measurement of three-phase, four-wire, 400-V line voltage.
Simple measurements without voltage wiring.
Incorrect voltage wiring detection.


...More relevant models >>>>