LK Automation Limited LK Automation Limited
Brand: OMRON
Go Back >> Product Catalogues
GT1-OD16MX Digital I/O Units
OMRON GT1-OD16MX Manual And Instructions
GT1-OD16MX datasheetPDF datasheet
GT1-OD16MX HOST CONNECTION MANUAL

OMRON GT1-OD16MX Product information and technical parameters:
Brand: OMRON
Name: Digital I/O Units
Model: GT1-OD16MX
Unit: Connector model.
I/O classification: Digital output.
Internal I/O common: NPN (- common).
I/O points: 16.
I/O connections: Molex connector.
Power supplyvoltage: 24 VDC.
I/O specification: 0.5 A, DC/transistor.
Digital I/O Units Compatible with MULTIPLE I/O TERMINAL,
Terminal block, connector, and high-density connector,
models are available.
The circuit block of the terminal block model can be,
mounted or dismounted for ease of maintenance without,
disconnecting the wires.
DIN track mounting.

Name: MIL Connectors.
Specifications: Outputs; 16 outputs ; PNP; --.
"Easy" and "Flexible" system expansion,
with linked CC-Link and CompoNet.
Branching is easily made with CompoNet.
Wiring material cost can be reduced.
Bit-level I/O distribution reduces,
wiring in the system.
A wide variety of CompoNet Slave Units,
contribute to system size reduction GT1-OD16MX.
Seven-segment Display on the Gateway Unit,
helps to detect errors on site GT1-OD16MX
The Participation Flags and Communications,
Error Flags can be checked at the Host,
Controller to detect the location and,
content of the error. Input capacity: 16 points.
Rated current (ON current): 0.5 A/output,
4.0 A/common.
Internal I/O common: NPN GT1-OD16MX.
Residual voltage: 1.2 V max.
(0.5 ADC, between each output,
terminal and the G terminal)
Leakage current: 0.1 mA max.
ON delay: 0.5 ms max.
OFF delay: 1.5 ms max.
Number of circuits per common:
8 points/common.
Output indicators: LED display (yellow).
Isolation method: Photocoupler isolation.
I/O power supply method: Supply by I/O power supply.
Output device supply current: 100 mA/point GT1-OD16MX.
Unit power supply current consumption: 90 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current consumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 370 g max.
Expansion functions: No.
Output handling for communications errors:
Select either hold or clear.
Short-circuit protection function: No.
A common terminal is provided for each contact.
It eliminate the needs for relay terminal blocks.
It is unnecessary to share the common terminal,
among multiple contacts.
Easy-to-find wiring locations.
Detachable screw terminal block facilitates the maintenance.
Input response time can be switched for high-speed processing.
Selectable node address setting methods: setting with rotary,
switch and with tool software.
When setting the nodes with rotary switch, setting is easy and,
node identification becomes possible for maintenance. Name: Expansion Units MIL Connector type.
Specifications:Digital inputs and outputs;
8 inputs/ 8 outputs; PNP;
One Expansion Unit can be mounted to one,
CRT1-VAD02@@D or CRT1-VDA02@@D Analog I/O Slave Unit.
Standards: --.
"Easy" and "Flexible" system expansion,
with linked CC-Link and CompoNet.
Branching is easily made with CompoNet.
Wiring materiaal cost can be reduced GT1-OD16MX.
Bit-level I/O distribution reduces,
wiring in the system.
A wide variety of CompoNet Slave Units,
contribute to system size reduction.
Seven-segment Display on the Gateway Unit,
helps to detect errors on sitee GT1-OD16MX.
The Participation Flags and Communications,
Error Flags can be checked at the Host,
Controller to detect the location and,
content of the error.


...More relevant models >>>>