OMRON E5EC-QR2DDM-810 Product information and technical parameters:
Brand: OMRON
Name: Simple digital temperature controller
Model: E5EC-QR2DDM-810
Type: plug - in.
Size: 48 x 96mm.
Control output 1: voltage output.
Control output 2: relay output.
Auxiliary output: 2 points.
Communication: -.
Heater break: 1.
Event input: 2 points.
Power supply voltage: AC/DC24V.
Using large font PV display (white), improve visibility.
Selection, setting and operation more simple and more group of input / output,
Functional performance is stronger, the function is more perfect and more extensive range of applications.
E5EC-800 white LCD-PV display height is about 18mm,
The E5AC-800 white LCD-PV display height is about 25mm improved visibility.
The main body is short, the thickness is only 60mm.
50ms high speed sampling period.
A new type of proportional control allows you to control the valve.

Size: 48 x 96mm.
Category: power AC100 ~ 240V with.
Shell color: black.
Control output 1: output unit mode.
Control output 2: output unit mode.
Control mode: standard or heating cooling.
Auxiliary output points: 2 points.
Heater break, SSR fault detection function: single phase or three phase heater detection function E5EC-QR2DDM-810.
Event entry point: 2.
Transfer output: -.
Remote SP:4 to 20mA input E5EC-QR2DDM-810
Communication: RS-232C.
New program type.
A new type of liquid crystal with high performance cost ratio is adopted in the 256 paragraph,
Visual angle, contrast can be improved.
Can be set up to 8 procedures (mode) x 32 (step) procedure.
High resolution 5 bit display / can display 0.01 degrees C.
High speed sampling period 60ms E5EC-QR2DDM-810.
All models complete a variety of (to the thermocouple /Pt/ analog input switching), 1 machines to support a variety of sensors.
Also supports remote SP.
Add PV/SV state display function, to see the state of the thermostat
(automatic / manual, RUN/RESET, alarm), interactive display PV/SV.
Through the support software (Ver.4.3 CX-Thermo) makes the process of setting management becomes very
Simple use of simple computing functions (AND/OR logic and delay) to set the implementation of flexible contact output E5EC-QR2DDM-810.
Through the infrared port can be carried out from the front of the communication.
The control output ON/OFF times counting function can predict the fault of the internal relay of the temperature controller. Case color: Black.
Control output: Voltage output (for driving SSR).
Control mode *1: Standard or heating/cooling.
No. of auxiliary outputs: 1.
Detection of heater burnout, SSR failure, and heater overcurrent: --.
No. of event inputs: 2.
Transfer output *2: --.
Communi cations: --.
Previous model: Thermocouple input, --;
Resistance thermometer input, --.
New 48 x 24-mm Basic Temperature,
Controller with Enhanced Functions and,
Performance. Improved Indication Accuracy,
and Preventive Maintenance Function.
Indication Accuracy.
Thermocouple input: ±0.3% of PV (previous models: ±0.5%),
Pt input: ±0.2% of PV (previous models: ±0.5%),
Analog input: ±0.2% FS (previous models: ±0.5%),
Models are available with screw terminal blocks or screwless,
clamp terminal blocks.
A PV/SV-status display function can be set to automatically alternate,
between displaying the status off the Temperature Controller (auto/
manual, RUN/STOP, and alarms) and the PV or SV E5EC-QR2DDM-810.
Preventive maintenance for relays in the Temperature,
Controller using a Control Output ON/OFF Counter.
Switch the PV display between three colorrs E5EC-QR2DDM-810.
Compatible with Support Software (CX-Thermo version 4.2 or higher).
Eleven-segment displays.
Models are available with one or two alarm outputs.