LK Automation Limited LK Automation Limited
Brand: OMRON
Go Back >> Product Catalogues
CJ1W-PRM21
OMRON CJ1W-PRM21 Manual And Instructions
CJ1W-PRM21 datasheetPDF datasheet

OMRON CJ1W-PRM21 Product information and technical parameters:
Brand: OMRON
Name:
Model: CJ1W-PRM21
Master unit provides data exchange, diagnostics and message communications.
Network type : Profibus-DP.
CJ1W-PRM21 Rating : 12 Mbps; 1200 m distance; 125 nodes; shielded twisted pair cable; allows 7, 168 words of I/O data per PLL; one RS-485 port.

Unit type: CJ1 Basic I/O Units.
Product name: Transistor Output Units.
Specifications: Output type, Sourcing;
I/O points, 32 outputs;
Maximum switching capacity, 24VDC,
0.5A Short-circuit protection;
Commons, 16 points, 1 common;
External connection, MIL connector.
No. of words allocated: 2 words CJ1W-PRM21.
Current consumption: 5V, 0.15A; 24V, --.
Standards: UC1, N, L, CE.
A Wide Range of Basic Output,
Units for High Speed Output,
and Different Applications CJ1W-PRM21
These Output Units receive the ,
results of output instructions ,
from the CPU Unit and perform ON/OFF,
control for external devices.
High-speed Output models CJ1W-OD213 and,
CJ1W-OD234 can help to increase system.
throughput CJ1W-PRM21. Unit type: CJ1 CPU Bus Units.
Product Name: Position Control,
Unit with MECHATROLINK-II interface.
Specifications: Control commands,
executed by MECHATROLINK-II,
synchronous communications.
Direct operation by ladder programming.
Control mode: Position control,
speed control or torque control;
No. of axes: 2 axes.
No. of unit numbers allocated: 1.
Current consumption : 5V, 0.36A; 24V,-- CJ1W-PRM21.
Standards: UC1, CE.
Decrease TCO with Simple Operation,
Reduced Wiring, Batch Settings,
and Batch Management.
Control Servos for up to 16 axes in,
a motion network with one Position,
Control Unit that supports MECHATROLINK-II.
MECHATROLINK-II is a registered trademark,
of the MECHATROLINK Members Association. Unit type: CJ1 Special I/O Units.
Product name: Analog Input Unit.
I/O points: 4 inputs;
Signal range selection: Set separately for each input.
Signal range; Resolution: 1 to 5 V (1/10,000),
0 to 10 V (1/20,000), -5 to 5 V (1/20,000),
-10 to 10 V (1/40,000), and 4 to 20 mA (1/10,000).
Conversion period: 20 μs/1 point, 25 μs/2 points,
30 μs/3 points, 35 μs/4 points,
The Direct conversion is provided.
Accuracy at ambient temperature of 25°C:
Voltage: ±0.2% of F.S. Current: ±0.4% of F.S.
Exterrnal connection: Removable terminal block CJ1W-PRM21.
No. of unit numbers allocated: 1.
Current consumption: 5V, 0.52A; 24V, --.
Standards: UC1, CE.
Consistent Microsecond Throughput:
Models with Direct Conversion Join the Lineup.
Analoog Input Units for converting analog input,
signals into binary data CJ1W-PRM21.
Analog Output Units for converting binary ,
data into analog output signals.