Input capacity: 32 points.
Internal I/O common: PNP.
ON voltage: 15 VDC min. (between each in,
put terminal and the G terminal).
OFF voltage: 5 VDC max. (between each in,
put terminal and the G terminal).
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0
F3SJ-A0305P205 ms,
1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms.
(Default setting: 1ms)
Number of circuits per common: 32 points/common.
Input indicators: LED display (yellow).
Isolation method: No isolation.
I/O power supply method: Supplied from unit power supply.
Input device supply current: 50 mA/point.
Unit power supply current consumption: 230 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 220 g max.
Expansion functions: No.
Short-circuit protection function: Available.
(Operates at 50 mA/point min.)
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors.
A common terminal is provided for,
each connector.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
switch and with tool software.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance. Safety outputs *1: Instantaneous, 2 (Semi conductors); OFF-delayed*2, 0.
Auxiliary outputs *3: 2 (Semi conductors).
Logical AND connection input: 1.
Logical AND connection output: 1.
Max. OFF delay time *4: --.
Rated voltage: 24 VDC.
Terminal block type: Spring-cage terminals.
Electronic Detection Mechanism for.
Better Stability in Non-contact Door.
Switch Operation. Number of beams: 84.
Protective height: 1680mm.
Safety Light Curtains with Durable,
Impact-resistant Body and Long,
20-m Sensing Distance.
MS/MSF4800A Advanced Series.
Programming and Diagnostics Module (PDM) makes it easy,
to set functions.
Series connection is possible only with the MSF4800A.
Blanking can be set.
Muting is possible only with the MSF4800A by using the,
MS4800-RM6 Resource Module.
MS/MSF4800B Basic Series,
Features all necessary basic Safety Light Curtain functions.
Series connection is possible only with the MSF4800B.
Programming and Diagnostics Module (PDM) makes it easy,
to set functions.
F3SJ-A0305P20 Operation manual/Instructions/Model selection sample download link:
/searchDownload.html?Search=F3SJ-A0305P20&select=5