Name: Basic Unit (temperature control) *1.
Power supply voltage: 24 VDC supplied from the End Unit.
No. of control points: 4.
Control outputs 1 and 2: Voltage output: 2 points (for SSR drive) *2.
Control outputs 3 and 4: Voltage output: 2 points (for SSR drive) *2.
Auxiliary output: None.
Functions: burnout Heater alarm, None; Event inputs, None .
Communications functions: G3ZA connection port: RS-485,
From End Unit: Port A or port B: RS-485
LY2I4 AC110/120
Input type: Thermocouple, platinum resistance thermometer,
analog voltage, and analog current selectable for each channel.
Terminal: M3 terminal.
In-panel Temperature Controller with Flexible,
Modular Design and Wide Integration with Host,
Devices.
The compact modular structure enables construction of temperature,
systems optimally suited to the application.
Connection can be made to a Programmable Controller without any,
programming required, reducing the number of steps required in ladder,
programming design.
One fully universal-input Unit includes a thermocouple, platinum-resistance,
thermometer, and analog input for easy selection and reduced inventory,
requirements.
Connect directly to the G3ZA Multi-channel Power Controller using,
optimum cycle control for high-accuracy regulation with minimal noise.
Autotuning (AT) can be used for independent heating/cooling PID control.
Self-tuning (ST) can be used to calculate the PID constants with the step,
response method.
Up to 16 Temperature Controllers can be connected to a single DeviceNet,
Communications Unit. Size: 48 * 48mm, terminal type.
Category: control output 1 point type (power supply AC100 ~ 240V).
Shell color: black.
Control output: relay output.
Control mode: standard or heating cooling.
Auxiliary output points: 2 points.
Heater break, SSR fault detection function: single phase or three phase heater detection function.
Event entry point: 2.
Transfer output: -.
Communication: RS-485.
New program type.
A new type of liquid crystal with high performance cost ratio is adopted in the 256 paragraph,
Visual angle, contrast can be improved.
Can be set up to 8 procedures (mode) x 32 (step) procedure.
High resolution 5 bit display / can display 0.01 degrees C (to achieve a small size of 48 x 48mm).
High speed sampling period 60ms.
Full of all models (capable of thermocouple /Pt/ analog input switching),
1 machines to support a variety of sensors.
Add PV/SV state display function, to see the state of the thermostat
(automatic / manual, RUN/RESET, alarm),
Interactive display PV/SV.
By supporting software (Ver.4.3 CX-Thermo),
In simple arithmetic functions (AND/OR logic and delay).
Setting the program settings that can perform flexible contact output.
The control output ON/OFF times counting function can predict the fault of the internal relay of the temperature controller.
LY2I4 AC110/120 Operation manual/Instructions/Model selection sample download link:
/searchDownload.html?Search=LY2I4 AC110/120&select=5