Power rating: 150 W.
Input voltage: 100 to 120 VAC, 200 to 240 VAC (allowable range: 90 to 132 VAC,
180 to 264 VAC, or 254 to 373 VDC(Select with the switch.)*2).
Output voltage: 48 V VDC.
Output current: 3.3 A.
Built-in fan: None.
Model with terminal block facing forward.
High Reliability at a Reasonable Cost S8EX-N01512L-CN1 Connection Guide.
Reliable, Basic Power Supplies That,
Contribute to Stable Equipment Operation
S8EX-N01512L-CN1
High Reliability: Enhanced abnormal overvoltage,
resistance and lightning surge resistance for stable,
operation even with an unstable input voltage.
Long Life: Japanese 105°C electrolytic capacitors are used,
to achieve stable quality and long life. A reliable 3-year warranty.
Wide Input Ranges: 100 to 120 VAC and 200 to 240 VAC,
Full Lineup: Models are available for the main output,
voltages and capacities used in FA applications S8EX-N01512L-CN1 Connection Guide.
Global Standards: Conforms to CE (all models),
Approved for UL (all models) and CCC (15 to 150-W models).
Easy mounting to DIN Rails with Mounting Brackets (sold separately).
Refer to Period and Terms of W. Specifications: Connector with DC line connected(For parallel operation) S8EX-N01512L-CN1 Connection Guide.
Number of Connectors: 10 Connectors (See note 4.).
Block-type Switch Mode Power Supply That.
Mounts to DIN Rail.
One model covers 30 to 120 W (12-V models).
One model covers 60 to 240 W (24-V models).
Easy creation of multi-power supply configurations with different,
output power supplies connected together (5-V, 12-V, and 24-Vmodels).
Improve power supply system reliability by creating N+1 redun,
dant systems (12-V and 24-V models).
RoHS-compliant.
Input conditions: 80 to 370 VDC supported for DC input too,
(EC Directives and safety standards are not applicable.)
Operating temperatures to –20°C (24-V models). Power ratings: 90 W.
Input voltage: 100 to 240 VAC(allowable range: 85 to 264 VAC or 80 to 370 VDC)*1.
Output voltage: 24 V.
Output current: 3.75 A.
Alarm output *2: Sinking.
UL Class 2 Output standards: --.
Model number(screwless terminal block).
60/90/120/180/240/480-W Models.
New Models with Indication.
Monitor and Simple Functions for.
Easy System Commissioning.
New 90-W models with indication monitor that.
conform to UL Class 2 Output standaards S8EX-N01512L-CN1 Manual.
New models with screwless terminal blocks and,
indication monitor.
Status displayed on 3-digit, 7-segment display.
Safety standards: UL 508/60950-1,
CSA C22.2 No. 107.1/60950-1,
EN 50178 (= VDE 0160), EN 60950-1 ((= VDE 0805 Teil 1) S8EX-N01512L-CN1 Manual.
Input conditions: DC input is also possible from 80 to 370 VDC.
(Not compliant with EC Directives and other safety standards.)