Appearance: Shielded, M18.
Sensing distance: 5 mm.
Output configuration : DC 2-wire.
Operation mode: NO.
Inductive Profoximity Sensor with.
Chemical-resistant Fluororesin Case.
Housing and mounting are made of Fluororesin resistant to chemicals.
Maximum sensing distance: 10 mm. Fitting materials: Iron, zinc plating E5EC-CX2ASM-014 Advanced Type.
Count: 1 .
Accessories: Description, Phillips screws M2
E5EC-CX2ASM-0143 × 8,
Spring washer M2.3;
Material, Iron, zinc plating, Iron, zinc plating;
Count, 4; 4 .
Applicable sensor (mounting pitch on sensor side): E3C-S10 (7.5).
Page: Dimensions, 12. Size: 48 x 96mm.
Category: power AC100 ~ 240V with.
Shell color: black.
Control output 1: built-in SSR output.
Control output 2: built-in SSR output E5EC-CX2ASM-014 Advanced Type.
Control mode: standard or heating cooling.
Auxiliary output points: 2 points.
The detection function of the broken wire and SSR fault of heater: detection function of single phase or three phase heater.
Event entry point: 2.
Transfer output: transfer output (special terminal).
Remote SP:4 to 20mA input.
Communication: RS-422.
General thermostat new high performance (high resolution, high speed, high precision input) type products E5EC-CX2ASM-014 Advanced Type.
Support simple operation, preventive maintenance.
A new type of liquid crystal, which can communicate with the front through the infrared port, is adopted,
Visual angle, contrast can be improved.
High resolution 5 bit display / can display 0.01 degrees C.
High speed sampling period 60ms.
All models complete a variety of (to the thermocouple /Pt/ analog input switching), 1 machines to support a variety of sensors.
Also supports remote SP.
Add PV/SV status display function, convenient to check the sstate of the thermostat (automatic / manual, RUN/STOP, alarm),
Interactive display PV/SV E5EC-CX2ASM-014 Manual.
By supporting software (Ver.4.0 CX-Thermo) to carry out a simple function (AND/OR logic and delay),
Be able to execute flexible contact output E5EC-CX2ASM-014 Manual.
Increase the control output ON/OFF number counting function, can predict the temperature controller internal relay fault.
Position ratio type.