CS1D-CPU42S INSTRUCTIONS REFERENCE MANUAL ()
Product model: CS1D-CPU42S
Name: PLC
Brand: OMRON
Sort: INSTRUCTIONS REFERENCE MANUAL
File language: English
Unit classification: CJ1 Special I/O Units.
Product name: ProcessInput Units,
(Isolated-type Thermocouple Input Units).
Input points: 2 inputs.
Signal range selection:
Set separately for each input.
Signal range: Thermocouple:
B, E, J, K, L, N, R, S, T, U,
WRe5-26, PLII DC voltage: ±100 mV CS1D-CPU42S INSTRUCTIONS REFERENCE MANUAL.
Conversion speed (resolution): Conversion,
speed: 10 ms/2 inputs, Resolution: 1/64,000 CS1D-CPU42S
Accuracy at ambient temperature of 25°C:
Standard accuracy: ±0.05% of F.S.
External connection: Removable terminal block.
No. of unit numbers allocated: 1.
Current consumption: 5V, 0.18A; 24V, 0.06A.
Standards: UC1, CE.
A Single Unit Handling All Types of Inputs,
such as Temperature Sensor Inputs and,
Analog Signal Inputs (e CS1D-CPU42S INSTRUCTIONS REFERENCE MANUAL. g., 4 to 20 mA or 1 to 5V).
A Unit supports four input channels,
each of which can be set to a
platinum resistance thermometer, thermocouple,
and DC signal (current, voltage).
All inputs are isolated. Unit type: CJ1 Basic I/O Units.
Product name: Transistor Output Units.
Specifications: Output type, Sinking;
I/O points, 16 outputs(High speed);
Maximum switching capacity, 24VDC, 0 CS1D-CPU42S INSTRUCTIONS REFERENCE MANUAL. 5A;
Commons, 16 points, 1 common;
External connection, Removable terminal block.
No. of words allocated: 1 word.
Current consumption: 5V, 0.15A; 24V, --.
Standards: N, L, CE.
A Wide Range of Basic Output,
Units for High Speed Output,
and Different Applications.
These Output Units receive the ,
results of output instructions ,
from the CPU Unit and perform ON/OFF,
control for external devices.
High-speed Output models CJ1W-OD213 and,
CJ1W-OD234 can help to increase system.
throughput. Unit type: CS1 Special I/O Units.
Product name: Isolated-type,
Thermocouple Input Units.
points Input: 8 inputs.
Signal range selection:
Set separately for each input.
I/O type: R, S, K, J, T, L, B.
Conversion speed: 250 ms/8 inputs.
Externa connection: Removable erminal block.
No. of unit numbers allocated: 1.
Current consumption: 5V, 0.18A; 26V, 0.06A.
Standards: UC1, CE.
Provides the functionality of isolators,
power supplies, signal converters,
and other devices.
The Analog Input Unit converts analog,
input signals such as 1 to 5 V or 4 to 20mA,
into digital values, and takes the values,
scaled in industrial units, and transfers,
it to the CPU Unit as the process value.
Because of this, no ladder program is required,
at the CPU Unit for scaling.
The Analog Output Unit converts analog output set,
values from the CPU Unit to analog output signals,
such as 4 to 20 mA or 1 to 5 V, and outputs them.
The built-in functions, such as measurement value,
alarms, rate-of-change calculations, and square roots,
have enabled major savings in cost and spaace compared,
with previous systems CS1D-CPU42S Manual.
High-resolution Models and 8-point Input Models are,
also available.
By combining the Units, logging/monitoring.
systems can be constructed,
or the Units can be used together with LCBs/LCCUs,
to construct complete process control systems CS1D-CPU42S Manual.
Parameters can be easily displayed and set in an,
easy-to-understand form without special tools.
Related products
OMRON
Programmable Controllers
CS1D-PA207R
OMRON Programmable Controllers CS1D-PA207R
Name: AC Power Supply Unit. Power suppl
OMRON
Programmable Controllers
CS1D-CPU65S
OMRON Programmable Controllers CS1D-CPU65S
Name: CS1D CPU Unit for Single CPU Syste
OMRON
CS1D-ETN21D
OMRON  CS1D-ETN21D
Connector: 100Base-TX. Communications s
OMRON
Programmable Controllers
CS1D-BC042D
OMRON Programmable Controllers CS1D-BC042D
Name: CS1D CPU Backplane. Specification